ASCE 7 Calculator

Deck Type
22 Guage or Heavier Steel
Membrane Type
TPO
Building Height
5 Feet
Exposure
B
Wind Speed Coefficient - Wind Speed-Up Over Hills, Ridges and Escarpments
1
Wind Speed Directionality
0.85
Basic Wind Speed (ASCE7 Hazard Tool / ATC Hazards by Location)
105 MPH
Risk Category (Choose based on Building Category and Location)
Category III
Safety Factor(SF) (Should be determined by your Architect or Specifier)
1
Internal Pressure(IP)
Enclosed Buildings

ASCE-7 Calculations

Field 0 Pressure
-10.9 PSF
Field Pressure
-19 PSF
Perimeter Pressure
-25.0 PSF
Corner Pressure
-34.1 PSF

Roof Design Type

Roof Design Type
Adhered System

Choose an adhered system design from the calculated uplift pressure to determine the number of fasteners or adhesive ribbon spacing to be used for that tested approval. For the complete code assembly refer to Carlisle Code Approval Guides for additional information.

Example: Test Approval Pressure = 90-PSF. One option would be to use 2” thick polyisocyanurate insulation fastened with 8 fastener and insulation plates per 4’ X 8’ size board.